# Network UPS Tools Binding
|
|
|
|
The primary goal of the [Network UPS Tools](https://networkupstools.org/) (NUT) project is to provide support for power devices, such as uninterruptible power supplies (UPS), Power Distribution Units and Solar Controllers.
|
|
|
|
Network UPS Tools (NUT) provides many control and monitoring features, with a uniform control and management interface.
|
|
More than 100 different manufacturers, and several thousands of models are compatible.
|
|
|
|
This binding lets you integrate NUT servers with openHAB.
|
|
|
|
## Supported Things
|
|
|
|
The binding can connect to multiple NUT instances.
|
|
The thing is an `ups` thing.
|
|
The thing supports a number of NUT features out-of-the-box and supports the option to configure additional channels to get other NUT variables.
|
|
The thing queries the NUT server for the status of the UPS approximate every 3 seconds and updates the status when a change happens.
|
|
When a change of the UPS status happens it will query the NUT server to update all linked channels.
|
|
Outside the status change updates, all linked channels are updated at the user configured refresh time.
|
|
|
|
Some NUT variables are static in nature and are not suited for a channel.
|
|
Some of these could change, like of firmware version.
|
|
Therefore these properties are updated with a 1 hour frequency.
|
|
The following NUT variables are read and added to the thing as properties:
|
|
|
|
| Property | Description |
|
|
| ---------------- | ------------------------- |
|
|
| ups.firmware | UPS firmware |
|
|
| ups.firmware.aux | Auxiliary device firmware |
|
|
| ups.id | UPS system identifier |
|
|
| ups.mfr | UPS manufacturer |
|
|
| ups.mfr.date | UPS manufacturing date |
|
|
| ups.model | UPS model |
|
|
| ups.serial | UPS serial number |
|
|
|
|
## Discovery
|
|
|
|
Discovery is not supported.
|
|
|
|
## Thing Configuration
|
|
|
|
The thing configuration requires the name of the UPS device as configured on the NUT server.
|
|
If the NUT service isn't running locally the ip address or domain name (FDQN) of the server running NUT must be configured.
|
|
Optional, port, username and password might need to be configured if required.
|
|
|
|
| Parameter | Default | Mandatory | Description |
|
|
| --------- | --------- | --------- | ----------------------------------------------- |
|
|
| device | | Yes | UPS device name, `ups` for example |
|
|
| host | localhost | Yes | UPS server hostname |
|
|
| port | 3493 | No | UPS server port, 3493 for example |
|
|
| username | | No | UPS server username |
|
|
| password | | No | UPS server password |
|
|
| refresh | 60 | No | Refresh interval for channel updates in seconds |
|
|
|
|
## Channels
|
|
|
|
The following channels are available:
|
|
|
|
| Channel Name | Item Type | Unit | Description | Advanced |
|
|
| ------------------- | ------------------------ | ---- | ------------------------------------------------------------------- | -------- |
|
|
| upsAlarm | String | | UPS alarms | no |
|
|
| upsLoad | Number:Dimensionless | % | Load on UPS (percent) | yes |
|
|
| upsPower | Number:Power | VA | Current value of apparent power (Volt-Amps) | yes |
|
|
| upsRealpower | Number:Power | W | Current value of real power (Watts) | no |
|
|
| upsStatus | String | | Status of the UPS: OFF, OL,OB,LB,RB,OVER,TRIM,BOOST,CAL,BYPASS,NULL | no |
|
|
| upsTemperature | Number:Temperature | °C | UPS temperature (degrees C) | yes |
|
|
| upsTestResult | String | | Results of last self test (opaque string) | yes |
|
|
| inputCurrent | Number:ElectricCurrent | A | Input current (A) | yes |
|
|
| inputCurrentStatus | String | | Status relative to the thresholds | yes |
|
|
| inputLoad | Number:Dimensionless | % | Load on (ePDU) input (percent of full) | no |
|
|
| inputRealpower | Number:Power | W | Current sum value of all (ePDU) phases real power (W) | yes |
|
|
| inputQuality | String | | Input power quality (*** opaque) | yes |
|
|
| inputTransferReason | String | | Reason for last transfer to battery (*** opaque) | yes |
|
|
| inputVoltage | Number:ElectricPotential | V | Input voltage (V) | yes |
|
|
| inputVoltageStatus | String | | Status relative to the thresholds | yes |
|
|
| outputCurrent | Number:ElectricCurrent | A | Output current (A) | yes |
|
|
| outputVoltage | Number:ElectricPotential | V | Output voltage (V) | yes |
|
|
| batteryCharge | Number:Dimensionless | % | Battery charge (percent) | no |
|
|
| batteryRuntime | Number:Time | s | Battery runtime (seconds) | no |
|
|
| batteryVoltage | Number:ElectricPotential | V | Battery voltage (V) | yes |
|
|
| batteryTemperature | Number:Temperature | °C | Battery temperature (degrees C) | yes |
|
|
|
|
### Dynamic Channels
|
|
|
|
Because there is a lot of variation in UPS features, the binding supports dynamically adding channels for features, not supported out-of-the-box.
|
|
To get data from another NUT variable the channel needs to configured.
|
|
Channels can be created with as type: `Number`, `Number:<Quantity>`, `String` or `Switch`.
|
|
|
|
The following channel properties are needed:
|
|
|
|
| Property | Description | Example |
|
|
| --------------- | ------------------------------ | --------------------------------------------- |
|
|
| networkupstools | Links to NUT variable | `networkupstools="input.voltage.low.warning"` |
|
|
| unit | The unit of Quantity Type data | `unit="V"` |
|
|
|
|
## Full Example
|
|
|
|
ups.things:
|
|
|
|
```java
|
|
Thing networkupstools:ups:ups1 [ device="ups", host="localhost", refresh=60 ]
|
|
```
|
|
|
|
ups-with-channels.things:
|
|
|
|
```java
|
|
Thing networkupstools:ups:ups2 [ device="ups", host="localhost", refresh=60 ] {
|
|
Channels:
|
|
String : testResult "Test Result" [networkupstools="ups.test.result"]
|
|
Number:Frequency : upsOutFreq "Output Frequency" [networkupstools="output.frequency", unit="Hz"]
|
|
Number:ElectricPotential : upsLowVoltage "Low Voltage" [networkupstools="input.voltage.low.warning", unit="V"]
|
|
Number:ElectricCurrent : upsLowCurrent "Low Current" [networkupstools="input.current.low.warning", unit="A"]
|
|
}
|
|
```
|
|
|
|
ups.items
|
|
|
|
```java
|
|
Number:Dimensionless ups_battery_charge "Battery Charge [%d %%]" {channel="networkupstools:ups:ups1:batteryCharge"}
|
|
Number:ElectricCurrent ups_current "Input Current [%d mA]"{channel="networkupstools:ups:ups1:inputCurrent"}
|
|
|
|
String test_result "Test Result" {channel="networkupstools:ups:ups2:testResult"}
|
|
Number:Frequency ups_out_freq "Output Frequency" {channel="networkupstools:ups:ups2:upsOutFreq"}
|
|
Number:ElectricPotential ups_low_voltage "Low Voltage [%.1f V]" {channel="networkupstools:ups:ups2:upsLowVoltage"}
|
|
Number:ElectricCurrent ups_low_current "Input Current [%d A]" {channel="networkupstools:ups:ups2:upsLowCurrent"}
|
|
```
|