# LCN Binding
|
|
|
|
[Local Control Network (LCN)](https://www.lcn.eu) is a building automation system.
|
|
It is capable of controlling lights, shutters, access control etc. and can process data from several sensor types.
|
|
It was introduced in 1992.
|
|
|
|
A broad range of glass key panels, displays, remote controls, sensors and in- and outputs exist.
|
|
The system can handle up to 30,000 bus members, called modules.
|
|
LCN modules are available for DIN rail and in-wall mounting and feature versatile interfaces.
|
|
The bus modules and most of the accessories are developed, manufactured and assembled in Germany.
|
|
|
|
Bus members are inter-connected via a free wire in the standard NYM cable.
|
|
Wireless components are available, though.
|
|
|
|
![Illustration of the LCN product family](doc/overview.jpg)
|
|
|
|
This binding uses TCP/IP to access the LCN bus via the software LCN-PCHK (Windows/Linux) or the DIN rail device LCN-VISU.
|
|
**This means 1 unused LCN-PCHK license or a LCN-VISU is required**
|
|
|
|
## Supported Things
|
|
|
|
### Thing: LCN Module
|
|
|
|
Any LCN module that should be controlled or visualized, need to be added to openHAB as a _Thing_.
|
|
|
|
LCN modules with firmware versions 120612 (2008), 170602 (2013) and 1F080A (2021) were tested with this binding.
|
|
Modules with older and newer firmware should work, too.
|
|
The module hardware types (e.g. LCN-SH, LCN-HU, LCN-UPP, ...) are compatible to each other and can therefore be handled all in the same way.
|
|
|
|
Thing Type ID: `module`
|
|
|
|
| Name | Description | Type | Required |
|
|
|-------------|----------------------------------------------------------------|---------|----------|
|
|
| `moduleId` | The module ID, configured in LCN-PRO | Integer | Yes |
|
|
| `segmentId` | The segment ID the module is in (0 if no segments are present) | Integer | Yes |
|
|
|
|
openHAB's discovery function can be used to add LCN modules automatically.
|
|
See [Discover LCN Modules](#discover-lcn-modules).
|
|
|
|
### Bridge: LCN PCK Gateway
|
|
|
|
PCK is the protocol spoken over TCP/IP with a PCK gateway to communicate with the LCN bus.
|
|
Examples for PCK gateways are the _LCN-PCHK_ software running on Windows or Linux and the DIN rail mounting device _LCN-VISU_.
|
|
|
|
For each LCN bus, interfaced to openHAB, a PCK gateway needs to be added to openHAB as a _Thing_.
|
|
|
|
Several PCK gateways can be added to openHAB to control multiple LCN busses in distinct locations.
|
|
|
|
The minimum recommended version is LCN-PCHK 3.3 (older versions will also work, but lack some functionality).
|
|
Visit [https://www.lcn.eu](https://www.lcn.eu) for updates.
|
|
|
|
Thing Type ID: `pckGateway`
|
|
|
|
| Name | Description | Type | Required |
|
|
|-------------|------------------------------------------------------------------------------------------------------------|---------|----------|
|
|
| `hostname` | Hostname or IP address of the LCN-PCHK gateway | String | Yes |
|
|
| `port` | TCP port of the LCN-PCHK gateway (default:4114) | Integer | Yes |
|
|
| `username` | Username configured within LCN-PCHK Monitor | String | Yes |
|
|
| `password` | Password configured within LCN-PCHK Monitor | String | Yes |
|
|
| `mode` | Dimmer resolution: `native50` or `native200` See below. | String | Yes |
|
|
| `timeoutMs` | Period after which an LCN command is resent, when no acknowledge has been received (in ms) (default: 3500) | Integer | Yes |
|
|
|
|
> **ATTENTION:** You must set the correct dimmer output resolution in the PCK Gateway Thing (`mode`)!
|
|
This setting is crucial, and valid for the **whole** LCN bus.<br />
|
|
It is either 0-50 steps or 0-200 steps.
|
|
It has to be the same as in the parameterizing software LCN-PRO under Options/Settings/Expert Settings.<br />
|
|
**When using a wrong dimmer output setting, dimming the outputs will result in unintended behavior!**
|
|
|
|
Please see the following LCN-PRO screenshot to determine the dimmer output resolution for the LCN bus:
|
|
|
|
![LCN-PRO screenshot, showing the 50 or 200 steps for the dimmer outputs](doc/LCN-PRO_output_steps.png)
|
|
|
|
### Thing: LCN Group
|
|
|
|
LCN modules can be assigned to groups with the programming software _LCN-PRO_.
|
|
|
|
To send commands to an LCN group, the group needs to be added to openHAB as a _Thing_.
|
|
|
|
One LCN module within the group is used to represent the status of the whole group.
|
|
For example, when a Dimmer Output is controlled via a LCN group _Thing_, openHAB will always visualize the state of the Dimmer Output of the chosen module. The states of the other modules in the group are ignored for visualization.
|
|
|
|
Thing Type ID: `group`
|
|
|
|
| Name | Description | Type | Required |
|
|
|-------------|----------------------------------------------------------------------------------------------------------------------------------------------|---------|----------|
|
|
| `groupId` | The group number, configured in LCN-PRO | Integer | Yes |
|
|
| `moduleId` | The module ID of any module in the group. The state of this module is used for visualization of the group as representative for all modules. | Integer | Yes |
|
|
| `segmentId` | The segment ID of all modules in this group (0 if no segments are present) | Integer | Yes |
|
|
|
|
The `groupId` must match the previously configured group number in the programming software _LCN-PRO_.
|
|
|
|
## Discovery
|
|
|
|
### Discover LCN Modules
|
|
|
|
Basic data like the names of all LCN modules in the bus, can be read out by openHAB's discovery function.
|
|
|
|
If not all LCN modules get listed on the first run, click on the refresh button to start another scan.
|
|
|
|
When adding a module by discovery, the new _Thing_'s UID will be a combination of segment and module id using the following format:
|
|
`S<segmentId>M<moduleId>` where `segmentId` and `moduleId` are formatted as three-digit numbers with leading zeros.
|
|
|
|
### Discover PCK Gateways
|
|
|
|
PCK gateways in the LAN can be found automatically by openHAB. This is done by UDP multicast messages on port 4220.
|
|
The discovery works only if the firewall of the PCK gateway is not configured too strictly.
|
|
This means on Windows PCs, that the network must be configured as 'private' and not as 'public'.
|
|
Also, some network switches may block multicast packets.
|
|
Unfortunately, _LCN-PCHK_ listens only on the first network interface of the computer for discovery packets.
|
|
If your PCK gateway has multiple network interfaces, _LCN-PCHK_ may listen on the wrong interface and fails to respond to the discovery request.
|
|
|
|
Discovery has successfully been tested with LCN-PCHK 3.2.2 running on a Raspberry Pi with Raspbian and openHAB running on Windows 10.
|
|
|
|
If discovery fails, you can add a PCK gateway manually. See [Thing: PCK Gateway](#bridge-lcn-pck-gateway).
|
|
|
|
Please be aware that you **have to configure** username, password and the dimmer output resolution also if you use discovery.
|
|
See [Thing: PCK Gateway](#bridge-lcn-pck-gateway).
|
|
|
|
When adding a PCK gateway by discovery, the new _Thing_'s UID is the MAC address of the device, running the PCK gateway.
|
|
|
|
## Supported LCN Features and openHAB Channels
|
|
|
|
The following table lists all features of LCN and their mappings to openHAB Channels.
|
|
These Channels are available for the _Thing_ LCN module (`module`).
|
|
LCN group (`group`) has the same Channels, except status-only Channels like binary sensors or transponders.
|
|
The PCK gateway (`pckGateway`) has no Channels.
|
|
|
|
Although, there are many **Not implemented** entries, the vast majority of LCN features can be used with openHAB:<br />
|
|
If a special command is needed, the [Hit Key](#hit-key) action (German: "Sende Tasten") can be used to hit a module's key virtually and execute an arbitrary command.
|
|
|
|
| LCN Feature (English) | LCN Feature (German) | Channel | IDs | Type | Description |
|
|
|---------------------------------|----------------------------------|------------------------|------|--------------------------------|-------------------------------------------------------------------------------------------------------------------------------|
|
|
| Dimmer Output Control Single | Ausgang | output | 1-4 | Dimmer, Switch | Sets the dimming value of an output with a given ramp. |
|
|
| Dimmer Output Control Color | Ausgang Farbe | output | color | Color, Switch | Sets the outputs 1-4 to control an RGBW lamp. |
|
|
| Tunable White Mode | Tunable White Modus | output | tunablewhite | String | Sets the module's tunable white mode: `DISABLE`: Tunable white disabled. `OUTPUT1`: Output 1 is used for controlling. Output 2 is adjusted automatically. `BOTH`: Output 1 is used to control the brightness. Output 2 controls the temperature. |
|
|
| Relay | Relais | relay | 1-8 | Switch | Controls a relay and visualizes its state. |
|
|
| Visualize Binary Sensor | Binärsensor anzeigen | binarysensor | 1-8 | Contact | Visualizes the state of a binary sensor (special channel mapping for some devices). |
|
|
| LED Control | LED-Steuerung | led | 1-12 | String | Controls an LED and visualizes its current state: `ON`, `OFF`, `BLINK`, `FLICKER` |
|
|
| Visualize Logic Operations | Logik Funktion anzeigen | logic | 1-4 | String | Visualizes the result of the logic operation: `NOT`, `OR`, `AND` |
|
|
| Motor/Shutter on Dimmer Outputs | Motor/Rollladen an Ausgängen | rollershutteroutput | 1-4 | Rollershutter | Control roller shutters on dimmer outputs |
|
|
| Motor/Shutter on Relays | Motor/Rollladen an Relais | rollershutterrelay | 1-4 | Rollershutter, Dimmer | Control position of roller shutters on relays (Supports UpDown, StopMove, Percent) |
|
|
| Shutter Slat Angle on Relays | Rollladenlamellen an Relais | rollershutterrelayslat | 1-4 | Rollershutter, Dimmer | Control slat angle of roller shutters on relays (Supports UpDown, StopMove, Percent) |
|
|
| Variables | Variable anzeigen | variable | 1-12 | Number | Sets and visualizes the value of a variable. See note. |
|
|
| Regulator Set Setpoint | Regler Sollwert ändern | rvarsetpoint | 1-2 | Number | Sets and visualizes the setpoint of a regulator. |
|
|
| Regulator Set Mode | Reglerverhalten ändern | rvarmode | 1-2 | String | Sets the mode of the regulator: `HEATING` or `COOLING` |
|
|
| Regulator Lock | Regler sperren | rvarlock | 1-2 | Switch | Locks a regulator and visualizes its locking state. |
|
|
| Set Thresholds in Register 1 | Schwellwert in Register 1 ändern | thresholdregister1 | 1-4 | Number | Sets and visualizes a threshold in the given threshold register. |
|
|
| Set Thresholds in Register 2 | Schwellwert in Register 2 ändern | thresholdregister2 | 1-4 | Number | Sets and visualizes a threshold in the given threshold register. |
|
|
| Set Thresholds in Register 3 | Schwellwert in Register 3 ändern | thresholdregister3 | 1-4 | Number | Sets and visualizes a threshold in the given threshold register. |
|
|
| Set Thresholds in Register 4 | Schwellwert in Register 4 ändern | thresholdregister4 | 1-4 | Number | Sets and visualizes a threshold in the given threshold register. |
|
|
| Visualize S0 Counters | S0-Zähler anzeigen | s0input | 1-4 | Number | Visualizes the value of a S0 counter. |
|
|
| Lock Keys Table A | Sperre Tastentabelle A | keylocktablea | 1-8 | Switch | Locks a key on the given key table and visualizes its state. |
|
|
| Lock Keys Table B | Sperre Tastentabelle B | keylocktableb | 1-8 | Switch | Locks a key on the given key table and visualizes its state. |
|
|
| Lock Keys Table C | Sperre Tastentabelle C | keylocktablec | 1-8 | Switch | Locks a key on the given key table and visualizes its state. |
|
|
| Lock Keys Table D | Sperre Tastentabelle D | keylocktabled | 1-8 | Switch | Locks a key on the given key table and visualizes its state. |
|
|
| Dimmer Output Flicker | Ausgang: Flackern | N/A | N/A | N/A | Action "flickerOutput": Let a dimmer output flicker for a given count of flashes. |
|
|
| Dynamic Text | Dynamischer Text | N/A | N/A | N/A | Action: "sendDynamicText": Sends custom text to an LCN-GTxD display. |
|
|
| Send Keys | Sende Tasten | N/A | N/A | N/A | Action: "hitKey": Hits a key of a key table in an LCN module. Can be used to execute commands, not supported by this binding. |
|
|
| Dimmer Output Control Multiple | Mehrere Ausgänge steuern | output | 1-4 | Dimmer, Switch | Control multiple outputs simultaneously. See below. |
|
|
| Transponder | Transponder | code#transponder | | Trigger | Receive transponder messages |
|
|
| Fingerprint | Fingerprint | code#fingerprint | | Trigger | Receive fingerprint code messages |
|
|
| Remote Control | Fernbedienung | code#remotecontrolkey | | Trigger | Receive commands from remote control |
|
|
| Access Control | Zutrittskontrolle | code#remotecontrolcode | | Trigger | Receive serial numbers from remote control |
|
|
| Remote Control Battery Low | Fernbedienung Batterie schwach | code#remotecontrolbatterylow | | Trigger | Triggered when the sending remote control has a low battery |
|
|
| Host Command (Send Keys) | Kommando an Host (Sende Tasten) | hostcommand#sendKeys | - | Trigger | Receive _send keys_ command from LCN module |
|
|
| Operating Hours Counter Outputs | Betriebsstundenzähler Ausgänge | operatinghourscounter | output[1-4] | Number:Time | Visualize Operating Hours Counter for outputs |
|
|
| Operating Hours Counter Outputs (rel. Work) | Betriebsstundenzähler Ausgänge (rel. Arbeit) | operatinghourscounter | outputrelativework[1-4] | Number:Time | Visualize Operating Hours Counter for outputs (relative work) |
|
|
| Operating Hours Counter Relays | Betriebsstundenzähler Relais | operatinghourscounter | relay[1-8] | Number:Time | Visualize Operating Hours Counter for relays |
|
|
| Operating Hours Counter Binary Sensor | Betriebsstundenzähler Binärsensoren | operatinghourscounter | binarysensor[1-8] | Number:Time | Visualize Operating Hours Counter for binary sensors |
|
|
| Status Message | Statusmeldungen | - | - | - | Automatically done by openHAB Binding |
|
|
| Audio Beep | Audio Piepen | N/A | N/A | N/A | Action: "beep" (see below) |
|
|
| Audio LCN-MRS | Audio LCN-MRS | - | - | - | Not implemented |
|
|
| Count/Compute | Zählen/Rechnen | - | - | - | Not implemented |
|
|
| DALI | DALI | - | - | - | Not implemented |
|
|
| Dimmer Output Memory Toggle | Ausgang: Memory Taster | - | - | - | Not implemented |
|
|
| Dimmer Output Ramp Stop | Ausgang: Rampe Stop | - | - | - | Not implemented |
|
|
| Dimmer Output Relative | Ausgang: Relativ | - | - | - | Not implemented |
|
|
| Dimmer Output Stairway | Ausgang: Treppenhauslicht | - | - | - | Not implemented |
|
|
| Dimmer Output Timer | Ausgang: Timer (Kurzzeit) | - | - | - | Not implemented |
|
|
| Display Set Language | Display-Sprache setzen | - | - | - | Not implemented |
|
|
| Dynamic Groups | Dynamische Gruppen | - | - | - | Not implemented |
|
|
| Free Input | Freie Eingabe | - | - | - | Not implemented |
|
|
| LED Brightness | LED-Helligkeit | - | - | - | Not implemented |
|
|
| LED Test | LED-Test | - | - | - | Not implemented |
|
|
| LED Transform | LED-Umwandlung | - | - | - | Not implemented |
|
|
| Light Scenes | Lichtszenen | - | - | - | Not implemented |
|
|
| Lock Keys by Time (Table A) | Sperre (Zeit) Tasten (Tabelle A) | - | - | - | Not implemented |
|
|
| Lock Outputs by Time | Sperre (Zeit) Ausgänge | - | - | - | Not implemented |
|
|
| Lock Relays | Sperre Relais | - | - | - | Not implemented |
|
|
| Lock Thresholds | Sperre Schwellwerte | - | - | - | Not implemented |
|
|
| Motor Position | Motor Position | - | - | - | Not implemented |
|
|
| Relay Timer | Relais-Timer | N/A | N/A | N/A | Action: "startRelayTimer" (see below) |
|
|
| Send Keys Delayed | Sende Tasten verzögert | - | - | - | Not implemented |
|
|
| Set S0 Counters | S0-Zähler setzen | - | - | - | Not implemented |
|
|
| Status Command | Statuskommandos | - | - | - | Not implemented |
|
|
|
|
_Notes:_
|
|
|
|
- **For some _Channel_s (e.g. temperature) a unit should be configured in the channel configuration.** By default the native LCN value is used.
|
|
- S0 counter Channels need to be the pulses per kWh configured. If the value is left blank, a default value of 1000 pulses/kWh is set.
|
|
- When setting a variable via openHAB, the variable must be configured as counter in LCN-PRO. The variable must be set initially by the module after power up.
|
|
- The Rollershutter Channels provide the boolean parameter `invertUpDown`, which can be set to 'true' if the Up/Down wires are interchanged.
|
|
- The binary sensor Channels provide the boolean parameter `invertState`, which can be set to 'true' if the binary sensor connected uses inverted logic for signaling open/closed.
|
|
|
|
### Transponder/Fingerprints
|
|
|
|
LCN transponder readers or fingerprint readers can be integrated in openHAB e.g. for access control.
|
|
The transponder function must be enabled in the module's I-port properties within _LCN-PRO_.
|
|
|
|
Example: When the transponder card with the ID "12ABCD" is seen by the reader connected to LCN module "S000M011", the item "M10_Relay7" is switched on:
|
|
|
|
```java
|
|
rule "My Transponder"
|
|
when
|
|
Channel "lcn:module:b827ebfea4bb:S000M011:code#transponder" triggered "12ABCD"
|
|
then
|
|
M10_Relay7.sendCommand(ON)
|
|
end
|
|
```
|
|
|
|
Example: When fingerprint with ID "AFFE12" is seen by reader connected to LCN module "S000M011", the item "M10_Relay7" is switched on:
|
|
|
|
```java
|
|
rule "My Fingerprint"
|
|
when
|
|
Channel "lcn:module:b827ebfea4bb:S000M011:code#fingerprint" triggered "AFFE12"
|
|
then
|
|
M10_Relay7.sendCommand(ON)
|
|
end
|
|
```
|
|
|
|
### Command from an LCN Module to openHAB
|
|
|
|
LCN modules can send commands to openHAB, e.g. by pressing a physical LCN key.
|
|
The command must be programmed into the LCN module by the programming software LCN-PRO.
|
|
Only the _send keys_ command (German: "Sende Tasten") is supported.
|
|
|
|
Program a command to a key of an LCN module via LCN-PRO.
|
|
When LCN-PRO asks you for the target address, don't select any module, but manually enter the PCK host ID, configured within PCHK (default: 4).
|
|
Select the _send keys_ command and "A-C (former command)", as PCHK 3.2.2 only supports the old command.
|
|
Then, select any key(s) you want to send to openHAB. These can be freely chosen, as they are only evaluated by openHAB.
|
|
|
|
![Screenshot, showing the send keys command](doc/host_command_send_keys.png)
|
|
|
|
The following rule can be used to trigger any action:
|
|
|
|
```java
|
|
rule "Module 12 sent A1 Hit"
|
|
when
|
|
Channel "lcn:module:b827ebfea4bb:S000M012:hostcommand#sendKeys" triggered "A1:HIT"
|
|
then
|
|
M10_Relay7.sendCommand(ON)
|
|
end
|
|
```
|
|
|
|
`A1` is the key of the _send keys_ command, programmed by LCN-PRO.
|
|
After the colon, the LCN "hit type" follows: HIT, MAKE or BREAK (German: kurz, lang, los)
|
|
|
|
If multiple keys or key tables are programmed in a single "send keys" command, multiple triggers will be executed.
|
|
|
|
> Notice: Don't test the command with the "Test command" button in LCN-PRO.
|
|
This will send a command from LCN-PRO to openHAB, but openHAB expects the module as the sender.
|
|
Simply press the physical button at the module for testing.
|
|
|
|
### Remote Control
|
|
|
|
To evaluate commands from LCN remote controls (e.g. LCN-RT or LCN-RT16), the module's I-port behavior must be configured as "IR access control" within _LCN-PRO_:
|
|
|
|
![Screenshot, showing the I-port properties for remote controls](doc/ir.png)
|
|
|
|
#### Remote Control Keys
|
|
|
|
The trigger _Channel_ `lcn:module:<pckThing>:<moduleThing>:code#remotecontrolkey` can be used to execute commands, when a specific key on a remote control is pressed:
|
|
|
|
```java
|
|
rule "Remote Control Key 3 on Layer 1 hit"
|
|
when
|
|
Channel "lcn:module:b827ebfea4bb:S000M012:code#remotecontrolkey" triggered "A3:HIT"
|
|
then
|
|
M10_Relay7.sendCommand(ON)
|
|
end
|
|
```
|
|
|
|
`A3` is key 3 on the first layer. `B1` is key 1 on the second layer etc.. After the colon follows the LCN "hit type" HIT, MAKE or BREAK (German: kurz, lang, los).
|
|
|
|
#### Remote Control used as Access Control
|
|
|
|
The serial number of a remote control can be used for access control via the channel `lcn:module:<pckThing>:<moduleThing>:code#remotecontrolcode`. See the following example:
|
|
|
|
```java
|
|
rule "Remote Control Key 3 on Layer 1 hit (only executed for serial number AB1234)"
|
|
when
|
|
Channel "lcn:module:b827ebfea4bb:S000M012:code#remotecontrolcode" triggered "AB1234:A3:HIT" or
|
|
Channel "lcn:module:b827ebfea4bb:S000M012:code#remotecontrolcode" triggered "AB1234:A3:MAKE"
|
|
then
|
|
M10_Relay7.sendCommand(ON)
|
|
end
|
|
```
|
|
|
|
The command will be executed when the remote control button A3 is either pressed short or long.
|
|
|
|
## Dimmer Outputs with Ramp and Multiple Outputs
|
|
|
|
The _output_ profile can be used to control multiple dimmer outputs of the _same_ module simultaneously or control a dimmer output with a ramp (slowly dimming).
|
|
|
|
The optional _ramp_ parameter must be float or integer.
|
|
The lowest value is 0.25, which corresponds to 0.25s. The highest value is 486s.
|
|
When no _ramp_ parameter is specified or no profile is configured, the ramp is 0 (behavior like a switch).
|
|
The ramp parameter is not available for Color _Item_s.
|
|
|
|
```java
|
|
// Dim output 2 in 0.25s
|
|
Switch M10_Output2 {channel="lcn:module:b827ebfea4bb:S000M010:output#2"[profile="lcn:output", ramp=0.25]} // with ramp of 0.25s (smallest value)
|
|
// Dim output 3 in 486s
|
|
Dimmer M10_Output3 {channel="lcn:module:b827ebfea4bb:S000M010:output#3"[profile="lcn:output", ramp=486]} // with ramp of 486s (biggest value)
|
|
```
|
|
|
|
The optional parameters _controlAllOutputs_ and _controlOutputs12_ can be used to control multiple outputs simultaneously.
|
|
Please note that the combination of these parameters with the _ramp_ parameter is limited:
|
|
|
|
```java
|
|
// Control outputs 1+2 simultaneously. Status of Output 1 is visualized. Only ramps of 0s or 0.25s are supported.
|
|
Dimmer M10_Outputs12a {channel="lcn:module:b827ebfea4bb:S000M010:output#1"[profile="lcn:output", controlOutputs12=true]}
|
|
Dimmer M10_Outputs12b {channel="lcn:module:b827ebfea4bb:S000M010:output#1"[profile="lcn:output", controlOutputs12=true, ramp=0.25]}
|
|
// Control all outputs simultaneously. Status of Output 1 is visualized.
|
|
Dimmer M10_OutputAll1 {channel="lcn:module:b827ebfea4bb:S000M010:output#1"[profile="lcn:output", controlAllOutputs=true, ramp=0]} // ramp only since firmware 180501
|
|
Dimmer M10_OutputAll2 {channel="lcn:module:b827ebfea4bb:S000M010:output#1"[profile="lcn:output", controlAllOutputs=true, ramp=0.25]} // ramp compatibility: all
|
|
Dimmer M10_OutputAll3 {channel="lcn:module:b827ebfea4bb:S000M010:output#1"[profile="lcn:output", controlAllOutputs=true, ramp=0.5]} // ramp only since firmware 180501
|
|
```
|
|
|
|
## Actions
|
|
|
|
Actions are special commands that can be sent to LCN modules or LCN groups.
|
|
|
|
### Hit Key
|
|
|
|
This _Action_ virtually hits a key of a key table in an LCN module.
|
|
Simply spoken, openHAB acts as a push button switch connected to an LCN module.
|
|
|
|
This _Action_ can be used to execute commands which are not natively supported by this binding.
|
|
The function can be programmed via the software _LCN-PRO_ onto a key in a module's key table.
|
|
Then, the programmed key can be "hit" by this _Action_ and the command will be executed.
|
|
|
|
When programming a "Hit Key" _Action_, the following parameters need to be set:
|
|
|
|
_table_ - The module's key table: A, B, C or D<br />
|
|
_key_ - The number of the key within the key table: 1-8<br />
|
|
_action_ - The key's action: HIT (German: "kurz"), MAKE ("lang") or BREAK ("los")
|
|
|
|
```java
|
|
rule "Hit key C4 hourly"
|
|
when
|
|
Time cron "0 0 * * * ?"
|
|
then
|
|
val actions = getActions("lcn","lcn:module:b827ebfea4bb:S000M010")
|
|
actions.hitKey("C", 4, "HIT")
|
|
end
|
|
```
|
|
|
|
### Dynamic Text
|
|
|
|
This _Action_ can be used to send custom texts to an LCN-GTxD display.
|
|
To make this function work, the row of the display has to be configured to allow dynamic text within _LCN-PRO_:
|
|
|
|
![Screenshot of LCN-PRO, showing the dynamic text setting of an LCN-GT10D](doc/dyn_text.png)
|
|
|
|
When programming a "Dynamic Text" _Action_, the following parameters need to be set:
|
|
|
|
_row_ - The number of the row in the display: 1-4<br />
|
|
_text_ - The text to be displayed (UTF-8)
|
|
|
|
The length of the text may not exceed 60 bytes of characters.
|
|
Bear in mind that unicode characters can take more than one byte (e.g. umlauts (äöü) take two bytes).
|
|
|
|
```java
|
|
rule "Send dynamic Text to GT10D hourly"
|
|
when
|
|
Time cron "0 0 * * * ?"
|
|
then
|
|
val actions = getActions("lcn","lcn:module:b827ebfea4bb:S000M012")
|
|
actions.sendDynamicText(1, "Test 123 CO₂ öäü߀") // row 1
|
|
end
|
|
```
|
|
|
|
### Flicker Output
|
|
|
|
This _Action_ realizes the LCN command "Output: Flicker" (German: "Ausgang: Flackern").
|
|
The command let a dimmer output flash a given number of times. This feature can be used e.g. for alert signals or visual door bells.
|
|
|
|
When programming a "Flicker Output" _Action_, the following parameters need to be set:
|
|
|
|
_output_ - The dimmer output number: 1-4<br />
|
|
_depth_ - The depth of the flickering: 0-2 (0=25% 1=50% 2=100% Example: When the output is fully on (100%), and 0 is selected, flashes will dim from 100% to 75% and back)<br />
|
|
_ramp_ - The duration/ramp of one flash: 0-2 (0=2sec 1=1sec 2=0.5sec)<br />
|
|
_count_ - The number of flashes: 1-15
|
|
|
|
This action has also effect, if the given output is off. The output will be dimmed from 0% to _depth_ and back, then.
|
|
|
|
```java
|
|
rule "Flicker output 1 when window opens"
|
|
when
|
|
Item M10_BinarySensor5 changed to OPEN
|
|
then
|
|
val actions = getActions("lcn","lcn:module:b827ebfea4bb:S000M010")
|
|
// output=1, depth=2=100%, ramp=0=2s, count=3
|
|
actions.flickerOutput(1, 2, 0, 3)
|
|
end
|
|
```
|
|
|
|
### Relay Timer
|
|
|
|
This _Action_ realizes the LCN commmand "Relay Timer" (German: "Relais-Timer").
|
|
The command switches the given relay immediately to on and after a given time back to off.
|
|
|
|
When programming a "Relay Timer" _Action_, the following parameters need to be set:
|
|
|
|
_relayNumber_ - The relay number: 1-8<br />
|
|
_duration_ - Timer duration in milliseconds: 30-240.000 ms<br />
|
|
|
|
```java
|
|
rule "Start relay timer for led driver when dummy switch changed"
|
|
when
|
|
Item Dummy_Switch changed
|
|
then
|
|
val actions = getActions("lcn","lcn:module:b827ebfea4bb:17B4196847")
|
|
// relayNumber=3, duration=90
|
|
actions.startRelayTimer(3, 90)
|
|
end
|
|
```
|
|
|
|
### Beep
|
|
|
|
This _Action_ realizes the LCN commmand "audio" (German: "Piepen").
|
|
It lets the beeper connected to the LCN module beep.
|
|
|
|
When programming an "audio" _Action_, the following parameters can be set:
|
|
|
|
_volume_ - Sound volume in percent (if null, the previous volume will be used)<br />
|
|
_tonality_ - The tonality as a String. You need to use quotes. See below.<br />
|
|
_count_ - Number of beeps (max. 50)
|
|
|
|
Tonalities:
|
|
|
|
- "N"=push button hit (normal)
|
|
- "S"=special
|
|
- "1"=push button make
|
|
- "2"=push button break
|
|
- "3"=standard
|
|
- "4"=special
|
|
- "5"=special short
|
|
- "6"=error
|
|
- "7"=long
|
|
|
|
```java
|
|
rule "Beep when dummy switch changed"
|
|
when
|
|
Item Dummy_Switch changed
|
|
then
|
|
val actions = getActions("lcn","lcn:module:b827ebfea4bb:b0b029b920")
|
|
// volume=100, tonality="6", count=2
|
|
actions.beep(100, "6", 2)
|
|
end
|
|
```
|
|
|
|
## Caveat and Limitations
|
|
|
|
LCN segments are supported by this binding, but could not be tested, due to lack of hardware.
|
|
|
|
LEDs do not support the _OnOffCommand_ and respectively the _Switch_ Item type, because they have the additional states _BLINK_ and _FLICKER_. They must be configured as _String_ Item. When used in rules, the parameter must be of type string. Example: `M10_LED1.sendCommand("ON")`. Note the quotation marks.
|
|
|
|
## Full Example
|
|
|
|
Config `.things`
|
|
|
|
```java
|
|
Bridge lcn:pckGateway:myPCHK [ hostname="192.168.123.123", port=4114, username="myUser", password="myPassword", mode="native200" ] {
|
|
Thing module M99 "M99 MyModule" [ moduleId=99, segmentId=0 ] {
|
|
Channels:
|
|
Rollershutter : rollershutterrelay#1 "My twisted rollershutter relay" [ invertUpDown = true ]
|
|
Contact : binarysensor#6 [ invertState=true ]
|
|
Number : rvarsetpoint#1 [ unit="temperature" ]
|
|
Number : variable#3 [ unit="temperature" ]
|
|
}
|
|
}
|
|
```
|
|
|
|
Config `.items`
|
|
|
|
```java
|
|
// Dimmer Outputs
|
|
Dimmer M10_Output1 {channel="lcn:module:b827ebfea4bb:S000M010:output#1"}
|
|
Switch M10_Output2 {channel="lcn:module:b827ebfea4bb:S000M010:output#2"[profile="lcn:output", ramp=0.25]} // with ramp of 0.25s (smallest value)
|
|
Dimmer M10_Output3 {channel="lcn:module:b827ebfea4bb:S000M010:output#3"[profile="lcn:output", ramp=486]} // with ramp of 486s (biggest value)
|
|
|
|
// Dimmer Outputs: Control all simultaneously. Status of Output 1 is visualized.
|
|
Dimmer M10_OutputAll1 {channel="lcn:module:b827ebfea4bb:S000M010:output#1"[profile="lcn:output", controlAllOutputs=true, ramp=0]} // ramp=0: only since firmware 180501
|
|
Dimmer M10_OutputAll2 {channel="lcn:module:b827ebfea4bb:S000M010:output#1"[profile="lcn:output", controlAllOutputs=true, ramp=0.25]} // ramp=0.25: compatibility: all firmwares
|
|
Dimmer M10_OutputAll3 {channel="lcn:module:b827ebfea4bb:S000M010:output#1"[profile="lcn:output", controlAllOutputs=true, ramp=0.5]} // ramp>=0.5: only since firmware 180501
|
|
|
|
// Dimmer Outputs: Control outputs 1+2 simultaneously. Status of Output 1 is visualized. Only ramps of 0s or 0.25s are supported.
|
|
Dimmer M10_Outputs12b {channel="lcn:module:b827ebfea4bb:S000M010:output#1"[profile="lcn:output", controlOutputs12=true, ramp=0.25]}
|
|
|
|
// Dimmer Outputs: RGB Control
|
|
Color M10_Color {channel="lcn:module:b827ebfea4bb:S000M010:output#color"[profile="lcn:output"]}
|
|
|
|
// Roller Shutter on Output 1+2
|
|
Rollershutter M10_RollershutterOutput1 {channel="lcn:module:b827ebfea4bb:S000M010:rollershutteroutput#1"}
|
|
|
|
// Relays
|
|
Switch M10_Relay1 {channel="lcn:module:b827ebfea4bb:S000M010:relay#1"}
|
|
|
|
// Roller Shutter on Relays 1+2
|
|
Rollershutter M10_RollershutterRelay1 {channel="lcn:module:b827ebfea4bb:S000M010:rollershutterrelay#1"}
|
|
Dimmer M10_RollershutterRelay1Slats {channel="lcn:module:68b8462b:S000M012:rollershutterrelayslat#1"}
|
|
|
|
// LEDs
|
|
String M10_LED1 {channel="lcn:module:b827ebfea4bb:S000M010:led#1"}
|
|
String M10_LED2 {channel="lcn:module:b827ebfea4bb:S000M010:led#2"}
|
|
|
|
// Logic Operations (legacy name: "Sums")
|
|
String M10_Logic1 {channel="lcn:module:b827ebfea4bb:S000M010:logic#1"}
|
|
String M10_Logic2 {channel="lcn:module:b827ebfea4bb:S000M010:logic#2"[profile="transform:MAP", function="alertSystem.map"]}
|
|
// conf/transform/alertSystem.map:
|
|
// NOT=All windows are closed
|
|
// OR=Some windows are open
|
|
// AND=All windows are open
|
|
|
|
// Binary Sensors (Channels 1-3 of LCN-B3I are mapped to BinarySensor6, BinarySensor7, BinarySensor8)
|
|
Contact M10_BinarySensor1 {channel="lcn:module:b827ebfea4bb:S000M010:binarysensor#1"}
|
|
|
|
// Variables
|
|
// The units of the variables must also be set in the Channels configuration, to be visualized correctly.
|
|
Number:Temperature M10_Variable1 "[%.1f %unit%]" <temperature> {channel="lcn:module:b827ebfea4bb:S000M010:variable#1"} // Temperature in °C
|
|
Number:Temperature M10_Variable2 "[%.1f °F]" <temperature> {channel="lcn:module:b827ebfea4bb:S000M010:variable#2"} // Temperature in °F
|
|
Number M10_Variable3 "[%d ppm]" <temperature> {channel="lcn:module:b827ebfea4bb:S000M010:variable#3"} // Indoor air quality in ppm
|
|
Number M10_Variable4 "[%d lx]" {channel="lcn:module:b827ebfea4bb:S000M010:variable#4"} // Illuminance in Lux
|
|
Number:Illuminance M10_Variable5 "[%.1f klx]" {channel="lcn:module:b827ebfea4bb:S000M010:variable#5"} // Illuminance in kLux
|
|
Number M10_Variable6 "[%.1f mA]" {channel="lcn:module:b827ebfea4bb:S000M010:variable#6"} // Electrical current in mA
|
|
Number M10_Variable7 "[%.1f V]" {channel="lcn:module:b827ebfea4bb:S000M010:variable#7"} // Voltage in V
|
|
Number M10_Variable8 "[%.1f m/s]" {channel="lcn:module:b827ebfea4bb:S000M010:variable#8"} // Wind speed in m/s
|
|
Number M10_Variable9 "[%.1f °]" {channel="lcn:module:b827ebfea4bb:S000M010:variable#9"} // position of the sun (azimuth or elevation) in °
|
|
Number M10_Variable10 "[%d W]" {channel="lcn:module:b827ebfea4bb:S000M010:variable#10"} // Current power of an S0 input in W
|
|
Number:Power M10_Variable11 "[%.1f kW]" {channel="lcn:module:b827ebfea4bb:S000M010:variable#11"} // Current power of an S0 input in kW
|
|
|
|
// Regulators
|
|
Number:Temperature M10_R1VarSetpoint "[%.1f %unit%]" <temperature> {channel="lcn:module:b827ebfea4bb:S000M010:rvarsetpoint#1"} // Temperature in °C
|
|
Switch M10_R1VarLock {channel="lcn:module:b827ebfea4bb:S000M010:rvarlock#1"} // Lock state of R1Var
|
|
|
|
// Thresholds
|
|
Number:Temperature M10_ThresholdRegister1_Threshold1 "[%.1f %unit%]" {channel="lcn:module:b827ebfea4bb:S000M010:thresholdregister1#1"} // Temperature in °C
|
|
Number:Temperature M10_ThresholdRegister4_Threshold2 "[%.1f %unit%]" {channel="lcn:module:b827ebfea4bb:S000M010:thresholdregister4#2"} // Temperature in °C
|
|
|
|
// S0 Counters
|
|
Number:Energy M10_S0Counter1 "[%.1f kWh]" {channel="lcn:module:b827ebfea4bb:S000M010:s0input#1"}
|
|
|
|
// Key Locks
|
|
Switch M10_KeyLockA1 {channel="lcn:module:b827ebfea4bb:S000M010:keylocktablea#1"}
|
|
Switch M10_KeyLockD5 {channel="lcn:module:b827ebfea4bb:S000M010:keylocktabled#5"}
|
|
```
|
|
|
|
Config `.sitemap`
|
|
|
|
```perl
|
|
sitemap lcn label="My home automation" {
|
|
Frame label="Demo Items" {
|
|
// Dimmer Outputs
|
|
Default item=M10_Output1 label="Output 1"
|
|
Default item=M10_Output2 label="Output 2"
|
|
Default item=M10_Output3 label="Output 3"
|
|
|
|
// Dimmer Outputs: Control all simultaneously. Status of Output 1 is visualized.
|
|
Default item=M10_OutputAll1 label="All Outputs ramp=0 since firmware 180501"
|
|
Default item=M10_OutputAll2 label="All Outputs ramp=250ms all firmwares"
|
|
Default item=M10_OutputAll3 label="All Outputs ramp>=500ms since firmware 180501"
|
|
|
|
// Dimmer Outputs: Control outputs 1+2 simultaneously. Status of Output 1 is visualized. Only ramps of 0s or 0.25s are supported.
|
|
Default item=M10_Outputs12a label="Outputs 1+2 Ramp=0"
|
|
Default item=M10_Outputs12b label="Outputs 1+2 Ramp=0.25s"
|
|
|
|
// Dimmer Outputs: RGB Control
|
|
Colorpicker item=M10_Color
|
|
|
|
// Roller Shutter on Outputs 1+2
|
|
Default item=M10_RollershutterOutput1 label="Roller Shutter on Output 1+2"
|
|
|
|
// Relays
|
|
Default item=M10_Relay1 label="Relay 1"
|
|
|
|
// Roller Shutter on Relays
|
|
Default item=M10_RollershutterRelay1 label="Roller Shutter on Relay 1-2"
|
|
Dimmer item=M10_RollershutterRelay1 label="Roller Shutter Position on Relay 1-2"
|
|
Default item=M10_RollershutterRelay1Slats label="Roller Shutter Slat Angle on Relay 1-2"
|
|
|
|
// LEDs
|
|
Switch item=M10_LED1 label="LED 1" mappings=[ON=ON, OFF=OFF] // Don't display "Blink" or "Flicker"
|
|
Switch item=M10_LED2 label="LED 2"
|
|
|
|
// Logic Operations (legacy name: "Sums")
|
|
Default item=M10_Logic1 label="Logic Operation 1"
|
|
Default item=M10_Logic2 label="Logic Operation 2"
|
|
|
|
// Binary Sensors (Channels 1-3 of LCN-B3I are mapped to BinarySensor6, BinarySensor7, BinarySensor8)
|
|
Default item=M10_BinarySensor1 label="Binary Sensor 1"
|
|
|
|
// Variables
|
|
Setpoint item=M10_Variable1 label="Variable 1"
|
|
Default item=M10_Variable2 label="Variable 2"
|
|
Default item=M10_Variable3 label="Variable 3"
|
|
Default item=M10_Variable4 label="Variable 4"
|
|
Default item=M10_Variable5 label="Variable 5"
|
|
Default item=M10_Variable6 label="Variable 6"
|
|
Default item=M10_Variable7 label="Variable 7"
|
|
Default item=M10_Variable8 label="Variable 8"
|
|
Default item=M10_Variable9 label="Variable 9"
|
|
Default item=M10_Variable10 label="Variable 10"
|
|
Default item=M10_Variable11 label="Variable 11"
|
|
|
|
// Regulators
|
|
Setpoint item=M10_R1VarSetpoint label="R1Var Setpoint" step=1 minValue=-10.0
|
|
Default item=M10_R1VarLock label="R1Var Lock" // Lock state of R1Var
|
|
|
|
// Thresholds
|
|
Setpoint item=M10_ThresholdRegister1_Threshold1 label="Threshold Register 1 Threshold 1"
|
|
Setpoint item=M10_ThresholdRegister4_Threshold2 label="Threshold Register 4 Threshold 2"
|
|
|
|
// S0 Counters
|
|
Default item=M10_S0Counter1 label="S0 Counter 1"
|
|
|
|
// Key Locks
|
|
Default item=M10_KeyLockA1 label="Locked State Key A1"
|
|
Default item=M10_KeyLockD5 label="Locked State Key D5"
|
|
}
|
|
}
|
|
```
|