* Add default translations for binding add-ons This makes the texts used by these add-ons translatable with Crowdin. To keep the PR simple, it only adds default translations for add-ons which do not yet have any default translations properties file. We can do follow up PRs for adding missing key/values to add-ons that already have these files or to remove duplications. There are several add-ons in this PR that do have non-English translation files, so I'll upload those to Crowdin when the PR is merged. Signed-off-by: Wouter Born <github@maindrain.net> |
||
---|---|---|
.. | ||
src/main | ||
NOTICE | ||
pom.xml | ||
README.md |
OpenTherm Gateway Binding
This binding is used to integrate the OpenTherm Gateway into openHAB. The OpenTherm Gateway is a module designed by Schelte Bron that is connected in between a boiler and a thermostat and communicates using the OpenTherm protocol.
More information on the OpenTherm Gateway device can be found at https://otgw.tclcode.com/
Supported Things
The OpenTherm Gateway binding currently only supports one thing, and that's the gateway itself.
Discovery
The binding does not support auto discovery.
Binding Configuration
The binding itself does not require any configuration.
Thing Configuration
The binding is designed to support various ways of connecting to the OpenTherm Gateway device, but currently only supports a TCP socket connection. The configuration settings for the thing are Hostname/IP address and Port, which are used to connect to the gateway, and an automatic connection retry interval in case the connection to the OpenTherm Gateway device is lost.
Parameter | Name | Description | Required | Default |
---|---|---|---|---|
ipaddress |
Hostname or IP address | The hostname or IP address to connect to the OpenTherm Gateway. | yes | |
port |
Port | The port used to connect to the OpenTherm Gateway. | yes | |
connectionRetryInterval |
Connection Retry Interval | The interval in seconds to retry connecting (0 = disabled). | yes | 60 |
Channels
The OpenTherm Gateway binding supports the following channels:
Channel Type ID | Item Type | Description | Access |
---|---|---|---|
roomtemp | Number:Temperature | Current sensed room temperature | R |
roomsetpoint | Number:Temperature | Current room temperature setpoint | R |
temperaturetemporary | Number:Temperature | Temporary override room temperature setpoint | R/W |
temperatureconstant | Number:Temperature | Constant override room temperature setpoint | R/W |
controlsetpoint | Number:Temperature | Central heating water setpoint set at boiler | R |
controlsetpointrequested | Number:Temperature | Central heating water setpoint requested by thermostat | R |
controlsetpointoverride | Number:Temperature | Central heating water setpoint configured at gateway | R/W |
controlsetpoint2 | Number:Temperature | Central heating 2 water setpoint set at boiler | R |
controlsetpoint2requested | Number:Temperature | Central heating 2 water setpoint requested by thermostat | R |
controlsetpoint2override | Number:Temperature | Central heating 2 water setpoint configured at gateway | R/W |
dhwtemp | Number:Temperature | Domestic hot water temperature | R |
tdhwset | Number:Temperature | Domestic hot water temperature setpoint | R |
overridedhwsetpoint | Number:Temperature | Domestic hot water temperature setpoint override | R/W |
flowtemp | Number:Temperature | Boiler water temperature | R |
returntemp | Number:Temperature | Return water temperature | R |
outsidetemp | Number:Temperature | Outside temperature | R/W |
waterpressure | Number:Pressure | Central heating water pressure | R |
ch_enable | Switch | Central heating enabled set at boiler | R |
ch_enablerequested | Switch | Central heating enabled requested by thermostat | R |
ch_enableoverride | Switch | Central heating enabled overridden at gateway | R |
ch2_enable | Switch | Central heating 2 enabled set at boiler | R |
ch2_enablerequested | Switch | Central heating 2 enabled requested by thermostat | R |
ch2_enableoverride | Switch | Central heating 2 enabled overridden at gateway | R |
ch_mode | Switch | Central heating active | R |
dhw_enable | Switch | Domestic hot water enabled | R |
dhw_mode | Switch | Domestic hot water active | R |
flame | Switch | Burner active | R |
modulevel | Number:Dimensionless | Relative modulation level | R |
maxrelmdulevel | Number:Dimensionless | Maximum relative modulation level | R |
fault | Switch | Fault indication | R |
servicerequest | Switch | Service required | R |
lockout-reset | Switch | Lockout-reset enabled | R |
lowwaterpress | Switch | Low water pressure fault | R |
gasflamefault | Switch | Gas or flame fault | R |
airpressfault | Switch | Air pressure fault | R |
waterovtemp | Switch | Water over-temperature fault | R |
oemfaultcode | Switch | OEM fault code | R |
diag | Switch | Diagnostics indication | R |
unsuccessfulburnerstarts | Number:Dimensionless | Unsuccessful burner starts | R |
burnerstarts | Number:Dimensionless | Burner starts | R |
chpumpstarts | Number:Dimensionless | Central heating pump starts | R |
dhwpvstarts | Number:Dimensionless | Domestic hot water pump/valve starts | R |
dhwburnerstarts | Number:Dimensionless | Domestic hot water burner starts | R |
burnerhours | Number:Dimensionless | Burner hours | R |
chpumphours | Number:Dimensionless | Central heating pump hours | R |
dhwpvhours | Number:Dimensionless | Domestic hot water pump/valve hours | R |
dhwburnerhours | Number:Dimensionless | Domestic hot water burner hours | R |
sendcommand | Text | Channel to send commands to the OpenTherm Gateway device | W |
Full Example
demo.things
Thing openthermgateway:otgw:1 [ ipaddress="192.168.1.100", port=8000, connectionRetryInterval=60 ]
demo.items
Number:Temperature RoomTemperature "Room temperature [%.1f °C]" <temperature> { channel="openthermgateway:otgw:1:roomtemp" }
Number:Temperature RoomSetpoint "Room setpoint [%.1f °C]" <temperature> { channel="openthermgateway:otgw:1:roomsetpoint" }
Number:Temperature TemporaryRoomSetpointOverride "Temporary room setpoint override [%.1f °C]" <temperature> { channel="openthermgateway:otgw:1:temperaturetemporary" }
Number:Temperature ConstantRoomSetpointOverride "Constant room setpoint override [%.1f °C]" <temperature> { channel="openthermgateway:otgw:1:temperatureconstant" }
Number:Temperature ControlSetpoint "Control setpoint [%.1f °C]" <temperature> { channel="openthermgateway:otgw:1:controlsetpoint" }
Number:Temperature ControlSetpointRequested "Control setpoint requested [%.1f °C]" <temperature> { channel="openthermgateway:otgw:1:controlsetpointrequested" }
Number:Temperature ControlSetpointOverride "Control setpoint override [%.1f °C]" <temperature> { channel="openthermgateway:otgw:1:controlsetpointoverride" }
Number:Temperature ControlSetpoint2 "Control setpoint 2 [%.1f °C]" <temperature> { channel="openthermgateway:otgw:1:controlsetpoint2" }
Number:Temperature ControlSetpoint2Requested "Control setpoint 2 requested [%.1f °C]" <temperature> { channel="openthermgateway:otgw:1:controlsetpoint2requested" }
Number:Temperature ControlSetpoint2Override "Control setpoint 2 override [%.1f °C]" <temperature> { channel="openthermgateway:otgw:1:controlsetpoint2override" }
Number:Temperature DomesticHotWaterTemperature "Domestic hot water temperature [%.1f °C]" <temperature> { channel="openthermgateway:otgw:1:dhwtemp" }
Number:Temperature DomesticHotWaterSetpoint "Domestic hot water setpoint [%.1f °C]" <temperature> { channel="openthermgateway:otgw:1:tdhwset" }
Number:Temperature DomesticHotWaterSetpointOverride "Domestic hot water setpoint override [%.1f °C]" <temperature> { channel="openthermgateway:otgw:1:overridedhwsetpoint" }
Number:Temperature BoilerWaterTemperature "Boiler water temperature [%.1f °C]" <temperature> { channel="openthermgateway:otgw:1:flowtemp" }
Number:Temperature ReturnWaterTemperature "Return water temperature [%.1f °C]" <temperature> { channel="openthermgateway:otgw:1:returntemp" }
Number:Temperature OutsideTemperature "Outside temperature [%.1f °C]" <temperature> { channel="openthermgateway:otgw:1:outsidetemp" }
Number:Pressure CentralHeatingWaterPressure "Central heating water pressure [%.1f bar]" { channel="openthermgateway:otgw:1:waterpressure" }
Switch CentralHeatingEnabled "Central heating enabled" <switch> { channel="openthermgateway:otgw:1:ch_enable" }
Switch CentralHeatingEnabledRequested "Central heating enabled requested" <switch> { channel="openthermgateway:otgw:1:ch_enablerequested" }
Switch CentralHeatingEnabledOverride "Central heating enabled override" <switch> { channel="openthermgateway:otgw:1:ch_enableoverride" }
Switch CentralHeating2Enabled "Central heating 2 enabled" <switch> { channel="openthermgateway:otgw:1:ch2_enable" }
Switch CentralHeating2EnabledRequested "Central 2 heating enabled requested" <switch> { channel="openthermgateway:otgw:1:ch2_enablerequested" }
Switch CentralHeating2EnabledOverride "Central 2 heating enabled override" <switch> { channel="openthermgateway:otgw:1:ch2_enableoverride" }
Switch CentralHeatingActive "Central heating active" <switch> { channel="openthermgateway:otgw:1:ch_mode" }
Switch DomesticHotWaterEnabled "Domestic hot water enabled" <switch> { channel="openthermgateway:otgw:1:dhw_enable" }
Switch DomesticHotWaterActive "Domestic hot water active" <switch> { channel="openthermgateway:otgw:1:dhw_mode" }
Switch BurnerActive "Burner active" <switch> { channel="openthermgateway:otgw:1:flame" }
Number:Dimensionless RelativeModulationLevel "Relative modulation level [%.1f %%]" { channel="openthermgateway:otgw:1:modulevel" }
Number:Dimensionless MaximumRelativeModulationLevel "Maximum relative modulation level [%.1f %%]" { channel="openthermgateway:otgw:1:maxrelmdulevel" }
Switch Fault "Fault indication" <switch> { channel="openthermgateway:otgw:1:fault" }
Switch ServiceRequest "Service required" <switch> { channel="openthermgateway:otgw:1:servicerequest" }
Switch LockoutReset "Lockout-reset" <switch> { channel="openthermgateway:otgw:1:lockout-reset" }
Switch LowWaterPress "Low water pressure fault" <switch> { channel="openthermgateway:otgw:1:lowwaterpress" }
Switch GasFlameFault "Gas or flame fault" <switch> { channel="openthermgateway:otgw:1:gasflamefault" }
Switch AirPressFault "Air pressure fault" <switch> { channel="openthermgateway:otgw:1:airpressfault" }
Switch WaterOvTemp "Water over-temperature fault" <switch> { channel="openthermgateway:otgw:1:waterovtemp" }
Number OemFaultCode "OEM fault code" { channel="openthermgateway:otgw:1:oemfaultcode" }
Switch Diagnostics "Diagnostics indication" { channel="openthermgateway:otgw:1:diag" }
Number:Dimensionless UnsuccessfulBurnerStarts "Unsuccessful burner starts" { channel="openthermgateway:otgw:1:unsuccessfulburnerstarts" }
Number:Dimensionless BurnerStarts "Burner starts" { channel="openthermgateway:otgw:1:burnerstarts" }
Number:Dimensionless CentralHeatingPumpStarts "Central heating pump starts" { channel="openthermgateway:otgw:1:chpumpstarts" }
Number:Dimensionless DomesticHotWaterPumpValveStarts "Domestic hot water pump/valve starts" { channel="openthermgateway:otgw:1:dhwpvstarts" }
Number:Dimensionless DomesticHotWaterBurnerStarts "Domestic hot water burner starts" { channel="openthermgateway:otgw:1:dhwburnerstarts" }
Number:Time BurnerHours "Burner hours" { channel="openthermgateway:otgw:1:burnerhours" }
Number:Time CentralHeatingPumpHours "Central heating pump hours" { channel="openthermgateway:otgw:1:chpumphours" }
Number:Time DomesticHotWaterPumpValveHours "Domestic hot water pump/valve hours" { channel="openthermgateway:otgw:1:dhwpvhours" }
Number:Time DomesticHotWaterBurnerHours "Domestic hot water burner hours" { channel="openthermgateway:otgw:1:dhwburnerhours" }
Text SendCommand "Send command channel" { channel="openthermgateway:otgw:1:sendcommand" }
demo.sitemap
sitemap demo label="Main Menu" {
Frame label="OpenTherm Gateway" {
Text item="RoomTemperature" icon="temperature" label="Room temperature [%.1f °C]"
Text item="RoomSetpoint" icon="temperature" label="Room setpoint [%.1f °C]"
Setpoint item="TemporaryRoomSetpointOverride" icon="temperature" label="Temporary room setpoint override [%.1f °C]" minValue="0" maxValue="30" step="0.1"
Setpoint item="ConstantRoomSetpointOverride" icon="temperature" label="Constant room setpoint override [%.1f °C]" minValue="0" maxValue="30" step="0.1"
Text item="ControlSetpoint" icon="temperature" label="Control setpoint [%.1f °C]"
Text item="ControlSetpointRequested" icon="temperature" label="Control setpoint requested [%.1f °C]"
Setpoint item="ControlSetpointOverride" icon="temperature" label="Control setpoint override [%.1f °C]" minValue="0" maxValue="100" step="1"
Text item="DomesticHotWaterTemperature" icon="temperature" label="Domestic hot water temperature [%.1f °C]"
Text item="DomesticHotWaterSetpoint" icon="temperature" label="Domestic hot water setpoint [%.1f °C]"
Setpoint item="DomesticHotWaterSetpointOverride" icon="temperature" label="Domestic hot water setpoint override [%.1f °C]" minValue="0" maxValue="100" step="0.1"
Text item="BoilerWaterTemperature" icon="temperature" label="Boiler water temperature [%.1f °C]"
Text item="ReturnWaterTemperature" icon="temperature" label="Return water temperature [%.1f °C]"
Setpoint item="OutsideTemperature" icon="temperature" label="Outside temperature [%.1f °C]" minValue="-40" maxValue="100" step="0.1"
Text item="CentralHeatingWaterPressure" icon="" label="Central heating water pressure [%.1f bar]"
Switch item="CentralHeatingEnabled" icon="switch" label="Central heating enabled"
Switch item="CentralHeatingEnabledRequested" icon="switch" label="Central heating enabled requested"
Switch item="CentralHeatingEnabledOverride" icon="switch" label="Central heating enabled override"
Switch item="CentralHeatingActive" icon="switch" label="Central heating active"
Switch item="DomesticHotWaterEnabled" icon="switch" label="Domestic hot water enabled"
Switch item="DomesticHotWaterActive" icon="switch" label="Domestic hot water active"
Switch item="BurnerActive" icon="switch" label="Burner active"
Text item="RelativeModulationLevel" icon="" label="Relative modulation level [%.1f %%]"
Text item="MaximumRelativeModulationLevel" icon="" label="Maximum relative modulation level [%.1f %%]"
Switch item="Fault" icon="" label="Fault indication"
Switch item="ServiceRequest" icon="" label="Service required"
Switch item="LockoutReset" icon="" label="Lockout-reset"
Switch item="LowWaterPress" icon="" label="Low water pressure fault"
Switch item="GasFlameFault" icon="" label="Gas or flame fault"
Switch item="AirPressFault" icon="" label="Air pressure fault"
Switch item="waterOvTemp" icon="" label="Water over-temperature fault"
Text item="OemFaultCode" icon="" label="OEM fault code"
Switch item="Diagnostics" icon="" label="Diagnostics indication"
Text item="UnsuccessfulBurnerStarts" icon="" label="Unsuccessful burner starts"
Text item="BurnerStarts" icon="" label="Burner starts"
Text item="CentralHeatingPumpStarts" icon="" label="Central heating pump starts"
Text item="DomesticHotWaterPumpValveStarts" icon="" label="Domestic hot water pump/valve starts"
Text item="DomesticHotWaterBurnerStarts" icon="" label="Domestic hot water burner starts"
Text item="BurnerHours" icon="" label="Burner hours"
Text item="CentralHeatingPumpHours" icon="" label="Central heating pump hours"
Text item="DomesticHotWaterPumpValveHours" icon="" label="Domestic hot water pump/valve hours"
Text item="DomesticHotWaterBurnerHours" icon="" label="Domestic hot water burner hours"
}
}