# Modbus Saia Burgess Controls Binding This binding interfaces the energy meter series ALD1 by Saia Burgess Controls (SBC) via Modbus. ## Supported Things The following Things are supported: - `ald1Unidirectional`: 1-phase 32A one-way energy meter ALD1D5FD00A3A00 - `ald1Bidirectional`: 1-phase 32A two-way energy meter ALD1B5FD00A3A00 ## Discovery This binding does not support discovery. ## Thing Configuration The following configuration parameter applys to `ald1Unidirectional` and `ald1Bidirectional`. | Name | Description | Type | Required | |---------------|------------------------------------------|---------|----------| | pollInterval | Time between polling the data in ms | Integer | yes | The Thing needs a Modbus serial slave Bridge to operate. One of the following serial settings need to be configured in the Bridge: - 9600 baud, 2 stop bit, no parity - 9600 baud, 1 stop bit, even parity - 9600 baud, 1 stop bit, odd parity ## Channels The following Channels apply to `ald1Unidirectional` and `ald1Bidirectional` if not stated otherwise. | Name | Type | Description | |---------------------|--------------------------|---------------------------------------------------------------| | total_energy | Number:Energy | Energy Total | | partial_energy | Number:Energy | Energy Counter Resettable (only unidirectional meter) | | feeding_back_energy | Number:Energy | Energy Feeding Back (only bidirectional meter) | | voltage | Number:ElectricPotential | Effective Voltage | | current | Number:ElectricCurrent | Effective Current | | active_power | Number:Power | Effective Active Power (negative numbers mean feeding back) | | reactive_power | Number:Power | Effective Reactive Power (negative numbers mean feeding back) | | power_factor | Number:Dimensionless | Power Factor | ## Full Example ### .items ```java Number:Energy ALD1_Total_Energy "[%.2f %unit%]" {channel="modbus:ald1Bidirectional:8b6e85623b:total_energy"} Number:Energy ALD1_Feeding_Back_Energy "[%.2f %unit%]" {channel="modbus:ald1Bidirectional:8b6e85623b:feeding_back_energy"} Number:ElectricPotential ALD1_Voltage "[%d %unit%]" {channel="modbus:ald1Bidirectional:8b6e85623b:voltage"} Number:ElectricCurrent ALD1_Current "[%.1f %unit%]" {channel="modbus:ald1Bidirectional:8b6e85623b:current"} Number:Power ALD1_Active_Power "[%.2f %unit%]" {channel="modbus:ald1Bidirectional:8b6e85623b:active_power"} Number:Power ALD1_Reactive_Power "[%.2f %unit%]" {channel="modbus:ald1Bidirectional:8b6e85623b:reactive_power"} Number:Dimensionless ALD1_Power_Factor "[%.2f]" {channel="modbus:ald1Bidirectional:8b6e85623b:power_factor"} ``` ### .sitemap ```perl sitemap ald1 label="ALD1 Energy Meter" { Default item=ALD1_Total_Energy label="Total Energy" Default item=ALD1_Feeding_Back_Energy label="Feeding Back Energy" Default item=ALD1_Voltage label="Voltage" Default item=ALD1_Current label="Current" Default item=ALD1_Active_Power label="Active Power" Default item=ALD1_Reactive_Power label="Reactive Power" Default item=ALD1_Power_Factor label="Power Factor" } ```