[knx] Improve documentation for DPT 1.009 (#14510)

Carryover from smarthomej/addons#73.

Also-by: Jan N. Klug github@klug.nrw

Signed-off-by: Holger Friedrich <mail@holger-friedrich.de>
This commit is contained in:
Holger Friedrich 2023-02-26 18:56:16 +01:00 committed by GitHub
parent d3d14d8b04
commit 60d70efce6
No known key found for this signature in database
GPG Key ID: 4AEE18F83AFDEB23

View File

@ -14,10 +14,6 @@ Since the protocol is identical, the KNX binding can also communicate with it tr
The KNX binding supports two types of bridges, and one type of things to access the KNX bus.
There is an _ip_ bridge to connect to KNX IP Gateways, and a _serial_ bridge for connection over a serial port to a host-attached gateway.
## Binding Configuration
The binding itself does not require any special configuration.
## Bridges
The following two bridge types are supported. Bridges don't have channels on their own.
@ -124,6 +120,9 @@ Note: After changing the DPT of already existing Channels, openHAB needs to be r
|-----------|---------------|-------------|
| ga | Group address | 1.009 |
*Attention:* Due to a bug in the original implementation, the states for DPT 1.009 are inverted (i.e. `1` is mapped to `OPEN` instead of `CLOSE`).
A change would break all existing installations and is therefore not implemented.
##### Channel Type "number"
| Parameter | Description | Default DPT |
@ -189,6 +188,9 @@ If from the KNX bus a `GroupValueRead` telegram is sent to a *-control Channel,
|-----------|---------------|-------------|
| ga | Group address | 1.009 |
*Attention:* Due to a bug in the original implementation, the states for DPT 1.009 are inverted (i.e. `1` is mapped to `OPEN` instead of `CLOSE`).
A change would break all existing installations and is therefore not implemented.
##### Channel Type "number-control"
| Parameter | Description | Default DPT |