# Pulse Width Modulation (PWM) Automation
|
||
|
|
||
|
This automation module implements [Pulse Width Modulation (PWM)](https://en.wikipedia.org/wiki/Pulse-width_modulation).
|
||
|
|
||
|
PWM can be used to control actuators continuously from 0 to 100% that only support ON/OFF commands.
|
||
|
E.g. valves or heating burners.
|
||
|
It accomplishes that by switching the actuator on and off with a fixed interval.
|
||
|
The higher the control percentage (duty cycle), the longer the ON phase.
|
||
|
|
||
|
Example: If you have an interval of 10 sec and the duty cycle is 30%, the output is ON for 3 sec and OFF for 7 sec.
|
||
|
|
||
|
This module is **unsuitable** for controlling LED lights as the high PWM frequency can't be met.
|
||
|
|
||
|
> Note: The module starts to work only if the duty cycle has been updated at least once.
|
||
|
|
||
|
## Modules
|
||
|
|
||
|
The PWM module can be used in openHAB's [rule engine](https://www.openhab.org/docs/configuration/rules-dsl.html).
|
||
|
|
||
|
This automation provides a trigger module ("PWM triggers") with one input Item: `dutycycleItem` (0-100%).
|
||
|
The module calculates the ON/OFF state and returns it.
|
||
|
The return value is used to feed the Action module "Item Action" aka "send a command", which controls the actuator.
|
||
|
|
||
|
To configure a rule, you need to add a Trigger ("PWM triggers") and an Action ("Item Action").
|
||
|
Select the Item you like to control in the "Item Action" and leave the command empty.
|
||
|
|
||
|
### Trigger
|
||
|
|
||
|
| Name | Type | Description | Required |
|
||
|
|-----------------|---------|----------------------------------------------------------------------------------------------|----------|
|
||
|
| `dutycycleItem` | Item | The Item (PercentType) to read the duty cycle from | Yes |
|
||
|
| `interval` | Decimal | The constant interval in which the output is switch ON and OFF again in sec. | Yes |
|
||
|
| `minDutyCycle` | Decimal | Any duty cycle below this value will be increased to this value | No |
|
||
|
| `maxDutycycle` | Decimal | Any duty cycle above this value will be decreased to this value | No |
|
||
|
| `deadManSwitch` | Decimal | The output will be switched off, when the duty cycle is not updated within this time (in ms) | No |
|
||
|
|
||
|
The duty cycle can be limited via the parameters `minDutycycle` and `maxDutyCycle`.
|
||
|
This is helpful if you need to maintain a minimum time between the switching of the output.
|
||
|
This is necessary for example for heating burners, which may not be switched on for very short times.
|
||
|
The on time is than increased to `minDutycycle`.
|
||
|
In this case one should also set a max duty cycle to prevent short off times.
|
||
|
It makes sense to apply these symmetrically e.g. 10%/90% or 20%/80%.
|
||
|
|
||
|
If the duty cycle is 0% or 100%, the min/max parameters are ignored and the output is switched ON or OFF continuously.
|
||
|
|
||
|
If the duty cycle Item is not updated within the dead-man switch timeout, the output is switched off, regardless of the current duty cycle.
|
||
|
The function can be used to save energy if the source of the duty cycle died for whatever reason and doesn't update the value anymore.
|
||
|
When the duty cycle is updated again, the module returns to normal operation.
|
||
|
|
||
|
> Note: The min/max ON/OFF times set via `minDutycycle` and `maxDutycycle` are not met if the dead-man switch triggers and recovers fast.
|
||
|
|
||
|
## Control Algorithm
|
||
|
|
||
|
This module is designed to respond fast to duty cycle changes, but at the same time maintain a constant interval and also the min/max ON/OFF parameters.
|
||
|
For that reason, the module might seem to act peculiarly in some cases:
|
||
|
|
||
|
- When the output is ON and the duty cycle is decreased, the output might switch off immediately, if applicable.
|
||
|
Example: The interval is 10 sec and the current duty cycle is 80%.
|
||
|
When the duty cycle is decreased to 20%, the output would switch off immediately, if it has been already ON for more than 2 sec.
|
||
|
- When the duty cycle is 0% for a short interval and then increased again, the output will only switch on when the new interval starts.
|
||
|
- When the duty cycle is 0% or 100% for more than a whole interval, a new interval will start as soon as the duty cycle is updated to a value other than 0%, respective 100%.
|
||
|
- The module starts to work only if the duty cycle Item has been updated at least once.
|